HRV Sizing Calculator - CFM for an HRV or ERV

    How many cfm does an HRV or ERV need? Floor area and bedrooms in, the IRC or ASHRAE 62.2 rate out, raised for part-time running and bathroom pickups, plus what the core saves.

    Parameters

    Enter data for calculations

    Heated and cooled area

    Bedrooms + 1 = design occupants

    Ask the building department

    Empty = 0, bath fans stay

    Empty = skip savings

    Empty = 70 F

    For the design-day load

    Base 65 F, for the season

    From your gas bill

    From the furnace label

    Form progress0 / 3 fields

    💡 Fill in all required fields to unlock the calculate button

    HRV and ERV size in cfm, from the code that applies to your house

    Floor area and bedrooms decide most of it. This HRV sizing calculator turns them into the balanced airflow a heat recovery or energy recovery ventilator has to move, under the IRC table and equation or under ASHRAE 62.2, then checks whether bathroom pickups or part-time running push the number higher. A 2,400 sq ft house with 3 bedrooms needs 54 cfm under the IRC equation and 102 cfm under ASHRAE 62.2.

    The problem: two published rules, one house, two answers almost twice apart. Buy a unit for the smaller one and it falls short wherever ASHRAE 62.2 is the rule. Buy for the larger one and you may pay for a box and ducts sized for air the local code never asked for.

    The way out: find out which rule your building department or your energy program enforces, size to that one, and then let the two checks that can only raise the number (part-time operation and bathroom exhaust) have their say. The calculator does all three and shows each step.

    From floor area to bathroom grilles

    1. Conditioned floor area - square feet inside the heated and cooled envelope. Leave out an unconditioned garage or attic.
    2. Bedrooms - the rules use bedrooms plus one as the expected number of people. A studio counts as one bedroom.
    3. Ventilation rule - IRC (Section M1505.4.3 of the model residential code) or ASHRAE 62.2 (the ventilation standard some energy programs and local amendments cite).
    4. Occupants (ASHRAE only, optional) - if more people live there than bedrooms plus one, each extra person adds 7.5 cfm.
    5. Run time (IRC only) - continuous, or a share of every 4-hour period. Less run time means a higher rate while running.
    6. Bathrooms on the ventilator - how many bathrooms the unit exhausts from instead of a bath fan. Each needs 20 cfm when the unit runs all the time.
    7. Heat recovery (optional) - the sensible recovery efficiency from the unit's listing, the outdoor design temperature, heating degree days, gas price and furnace efficiency, to see what the core saves.

    IRC or ASHRAE 62.2: which number to size for

    Both rules start from the same 7.5 cfm per person. The difference is the area term: 0.01 cfm per square foot in the IRC equation against 0.03 cfm in ASHRAE 62.2. On a big house that gap dominates. The figures below come straight from the calculator, continuous operation, no bathroom pickups.

    HouseIRC equationIRC tableASHRAE 62.2
    900 sq ft, 1 bedroom243042
    1,525 sq ft, 2 bedrooms37.86068.3
    2,400 sq ft, 3 bedrooms5460102
    3,500 sq ft, 4 bedrooms72.590142.5
    5,000 sq ft, 5 bedrooms95105195

    The IRC lets you use either its table or its equation, so the calculator takes the lower of the two. The table works in floor-area bands (up to 1,500 sq ft, 1,501 to 3,000 and so on) and bedroom pairs, which is why it sometimes lands well above the equation, as on the 1,525 sq ft house that just crosses into the second band. The ASHRAE figure for that house, 68.25 cfm, is the worked example ACCA published for the formula.

    Three things that push the airflow up

    Running part of the time. The IRC allows a ventilator on a timer if it moves more air while it is on. Table M1505.4.3(2) gives the multiplier: 1.3 at 75% run time, 1.5 at 66%, 2 at 50%, 3 at 33% and 4 at 25% of each 4-hour period. The 2,400 sq ft house goes from 54 cfm continuous to 108 cfm at half time and 162 cfm at a third.

    Bathrooms on the ventilator. A bathroom needs 20 cfm of continuous exhaust or 50 cfm intermittent. When the HRV or ERV replaces the bath fans, its exhaust side has to cover 20 cfm per bathroom. A 1,200 sq ft, 2 bedroom house under the IRC needs only 34.5 cfm for the whole house, but with three bathroom pickups the unit has to move 60 cfm.

    More people than bedrooms. Under ASHRAE 62.2 a known occupancy above bedrooms plus one adds 7.5 cfm a head. A 1,800 sq ft, 3 bedroom house is 84 cfm for four people and 99 cfm for six.

    Matching the result to your job

    Your situationSize for
    Local code follows the IRC, no energy programThe IRC result, continuous operation
    Energy program or local amendment cites ASHRAE 62.2The ASHRAE result, unless a blower door test earns a credit
    Unit on a timer or cycling with the furnace fanThe run-time line, which can be two to four times the continuous rate
    Ventilator replaces the bath fansAt least 20 cfm per bathroom on the exhaust side, running continuously
    Two candidate units both clear the numberCompare rated airflow at your real duct static pressure, not the free-air maximum on the box

    What the heat recovery core is worth

    Every cubic foot of outdoor air has to be heated to room temperature, at 1.08 Btu/hr per cfm per degree F. The core hands part of that back from the stale air on its way out; the share is the sensible recovery efficiency (SRE) printed in the unit's listing. Enter it and the calculator shows both the design-day load and the season.

    ASHRAE 102 cfm, 75% SRE, 5 F outside

    Fresh air needs 7,160 Btu/hr to reach 70 F; the core returns 5,370 Btu/hr.

    Same house, 6,000 heating degree days

    119 therms of heat kept, about $188 a year with a 95% furnace at $1.50 a therm.

    IRC 54 cfm, same settings

    2,843 Btu/hr on the design day and about $99 a year: half the air, half the saving.

    The savings leave out the electricity the two fans use, defrost cycles in deep cold and duct losses, so treat them as the ceiling of what the core can do.

    HRV sizing questions

    Does this work for an ERV as well as an HRV?

    Yes. The code sets the outdoor airflow, not the type of core, so the cfm is the same. An ERV also moves moisture, which matters for comfort and for its total recovery figure, but the airflow you size for does not change.

    Why is the IRC number lower than ASHRAE 62.2?

    The area term. ASHRAE 62.2 counts 3 cfm per 100 sq ft, the IRC equation 1 cfm. The per-person part is identical, so the gap grows with floor area: 30 cfm on a 1,500 sq ft house, 100 cfm on 5,000 sq ft.

    Should I buy a unit rated exactly at the result?

    Look at the airflow listed at the static pressure your ducts will create, not the highest figure on the box. The result is the minimum the installer must measure at the grilles after balancing, so the unit has to reach it on a speed setting you can live with for noise.

    Can the ventilator take over from the bathroom fans?

    Codes allow an HRV or ERV exhaust grille to serve a bathroom in place of a local fan if it pulls 20 cfm continuously. On a timer it does not count as continuous, so each bathroom would then need 50 cfm on demand, from a boost switch or its own fan.

    Where do I find heating degree days for my town?

    NOAA publishes heating degree days, base 65 F, for weather stations across the country. Use the yearly total for the station nearest to you; the 6,000 in the example is only an illustration.

    What about the kitchen?

    The calculator leaves it out. Kitchens have their own local exhaust requirement in the codes (IRC Table M1505.4.4), sized separately from the whole-house rate.

    Related tools

    Radiant Floor Heating Calculator

    Btu per sq ft, floor surface temperature, feet of PEX and circuits for a room - See the calculator

    Heat Loss Calculator

    Design heat loss of a room or house in Btu/hr, air leakage line included - See the calculator

    Baseboard Heat Calculator

    Feet of hot water or electric baseboard for a room from its heat loss - See the calculator

    Insulation Calculator

    How much insulation the walls or attic need - See the calculator

    Chimney Draft Calculator

    Draft for a stove or fireplace, which a tight, ventilated house can weaken - See the calculator

    Gas Bill Calculator

    Monthly gas cost from usage and rates - See the calculator

    Heat Pump COP Calculator

    Efficiency of a heat pump at a given outdoor temperature - See the calculator

    Air Conditioner Size Calculator

    Cooling capacity for the same house, in Btu and tons - See the calculator

    Similar calculators from this section