Baseboard Heat Calculator - Feet of Hydronic or Electric

    How many feet of baseboard does the room need? Enter its heat loss in Btu/hr and get the length of hot water baseboard at your water temperature, or the watts, feet and amps of electric heat.

    Parameters

    Enter data for calculations

    From a heat loss calculation

    Hot water or electric

    Empty = no fit check

    Form progress0 / 2 fields

    💡 Fill in all required fields to unlock the calculate button

    How many feet of baseboard heat a room needs

    Type the room heat loss in Btu per hour, choose hot water or electric baseboard, and this baseboard heat calculator returns the length to install. For hot water it reads the manufacturer's rating at your water temperature; for electric it converts to watts, feet, amps and heater sizes. A room losing 6,000 Btu/hr needs 11 ft of hot water baseboard at 180 F, 20 ft at 140 F, or 1,758 W of electric heat, about 8 ft at 240 V.

    Add the free wall length under windows and along outside walls and the result also says whether the baseboard fits.

    580
    Btu/hr per ft of hot water baseboard at 180 F, 1 gpm
    250 W
    per ft of a typical electric baseboard at 240 V
    3.412
    Btu/hr in one watt of electric heat
    5-6 in.
    of each run that has no fins and gives little heat

    Three answers and two choices

    1. Room heat loss - Btu/hr for this room at the design temperature. Work it out room by room with a heat loss calculator; a whole-house figure divided by the floor area misses corner rooms and big windows.
    2. Hot water or electric - hydronic baseboard fed by a boiler, or electric baseboard heaters wired to a circuit.
    3. Water temperature and flow (hot water) - the average of supply and return, 110 to 220 F. 1 gpm unless the loop is known to carry 4 gpm or more.
    4. Voltage (electric) - 240 V in most houses, 208 V in many apartment buildings.
    5. Free wall (optional) - feet of wall where baseboard can go, usually under windows and along outside walls.

    The hot water ratings, temperature by temperature

    The calculator uses Slant/Fin's published ratings for its Fine/Line 30 baseboard with a 3/4 in. element: Btu/hr per foot of finned length, with 65 F air entering at the bottom and the 15% heating effect factor included. The right-hand columns show what the same 6,000 Btu/hr room needs at each temperature.

    Average water1 gpm4 gpmActive ft, 6,000 Btu/hrBaseboard to buy
    110 F16016037.538 ft
    120 F21022028.630 ft
    130 F26027023.124 ft
    140 F32034018.820 ft
    150 F38040015.817 ft
    160 F45048013.314 ft
    170 F51054011.813 ft
    180 F58061010.311 ft
    190 F6406809.410 ft
    200 F7107508.59 ft
    210 F7708107.89 ft
    215 F8108607.48 ft
    220 F8408907.18 ft

    Two patterns stand out. Output falls faster than the temperature: going from 180 F to 140 F, a cut of under a quarter, takes away 45% of the output (580 to 320). And the 4 gpm column barely helps, so the manufacturer allows it only when the flow is known to reach 4 gpm. Other baseboards and the 1/2 in. element rate differently, so use the table for the model you buy.

    Rooms by heat loss, sorted by what they need

    Small, well insulated: 1,734 Btu/hr

    A corner bedroom with heated rooms above and below. Hot water at 180 F: 4 ft (3.0 ft active). Electric: 508 W, about 3 ft.

    Typical room: 3,000 Btu/hr

    Hot water at 180 F: 6 ft (5.2 ft active). One 4 ft electric heater at 240 V gives 3,412 Btu/hr and covers it.

    Large or exposed: 6,000 Btu/hr

    Hot water: 11 ft at 180 F, 30 ft at 120 F. Electric: 1,758 W, 8 ft at 240 V or 10 ft at 208 V.

    Living room with big windows: 9,000 Btu/hr

    Hot water: 17 ft at 180 F (15.5 ft active), 21 ft at 160 F.

    Addition or bonus room: 12,000 Btu/hr

    Electric: 3,517 W, about 15 ft at 240 V and 14.7 A; the circuit is sized for 125% of that.

    Electric baseboard heater sizes at 240 V and 208 V

    Wattage per foot comes from a common 4 ft heater rated 1,000 W at 240 V and 750 W on 208 V. A heater's output falls with the square of the voltage, which is why the same unit loses a quarter of its heat on a 208 V supply.

    LengthW at 240 VBtu/hr at 240 VW at 208 VBtu/hr at 208 V
    2 ft5001,7063751,280
    4 ft1,0003,4127502,559
    6 ft1,5005,1181,1253,839
    8 ft2,0006,8241,5005,118

    Some models pack more watts into the same length, so read the label: the calculator's foot count assumes 250 W per foot at 240 V. The National Electrical Code treats fixed electric space heating as a continuous load, so the branch circuit is sized for 125% of the heaters' current.

    Why active length is shorter than the cover

    Hot water ratings are per foot of finned element, which stops 5 to 6 in. short of the overall length of the enclosure. The calculator divides the heat loss by the rating to get the finned length, adds half a foot and rounds up to a whole foot, the way baseboard is sold. On runs broken into several pieces, each piece loses its own unfinned ends, so allow a little more.

    Questions about sizing baseboard

    How many feet of baseboard heat do I need per room?

    Divide the room's heat loss by the baseboard rating at your water temperature. At 180 F that is heat loss / 580 in finned feet plus about half a foot, so a 3,000 Btu/hr room needs 6 ft and a 6,000 Btu/hr room 11 ft. A feet-per-square-foot rule ignores insulation and windows, which is where most of the difference between rooms comes from.

    Will my baseboard work with a heat pump or a condensing boiler?

    Only if there is enough of it. Both run best with cooler water, and at 120 F each foot gives 210 Btu/hr instead of 580, so the same room needs about 2.8 times as much baseboard. Run the calculator at 120 or 130 F and compare with the length already on the wall; lowering the room's heat loss first narrows the gap.

    What average water temperature should I use?

    The average of supply and return at design conditions. A boiler set to 180 F supply with a 20 F drop averages 170 F, and hot water baseboard has traditionally been sized around 180 F. If you are unsure, check the boiler's high limit and the temperature drop the system was designed for.

    How many watts of electric baseboard per square foot?

    There is no fixed figure, because it depends on the heat loss. Convert the room's Btu/hr to watts by dividing by 3.412: the 1,734 Btu/hr bedroom needs 508 W, the 12,000 Btu/hr addition 3,517 W. Heater coverage claims on boxes assume an average room and can be far off for a cold one.

    Where should the baseboard go?

    Along outside walls and under windows, where the cold comes in, so the warm air rising from the baseboard meets the cold air falling from the glass. Keep furniture and long drapes clear of the fins, or the output drops.

    Related tools

    Heat Loss Calculator

    The room heat loss in Btu/hr that this calculator starts from - See the calculator

    Chimney Draft Calculator

    Draft for the flue of an oil or gas boiler - See the calculator

    Electrical Cable Calculator

    Wire size for the circuit that feeds electric baseboard - See the calculator

    Distribution Board Calculator

    Panel space and breakers for new heating circuits - See the calculator

    Heat Pump COP Calculator

    Efficiency when a heat pump supplies the hot water - See the calculator

    Electricity Bill Calculator

    What the watts of electric baseboard cost to run - See the calculator

    Insulation Calculator

    Cut the heat loss, and the baseboard needed, before buying - See the calculator

    Similar calculators from this section