Will the chimney pull? Enter height, flue size and outdoor temperature to get the draft in inches of water column, checked against wood stove, oil and gas targets and code flue rules.
Chimney Draft Calculator - Draft in Inches of Water Column
Will the chimney pull? Enter height, flue size and outdoor temperature to get the draft in inches of water column, checked against wood stove, oil and gas targets and code flue rules.
Parameters
Enter data for calculations
💡 Fill in all required fields to unlock the calculate button
Chimney draft in inches of water column, from height and temperature
Pick the appliance, enter the chimney height and the outdoor temperature, and this chimney draft calculator returns the theoretical draft in inches of water column and pascals, compares it with the range stove and burner manuals ask for, and shows how the same chimney behaves from a cold night to a hot afternoon. A wood stove on a straight 15 ft chimney at 32 F, with flue gas averaging 400 F, pulls 0.100 in. w.c. (24.8 Pa).
The result also checks two code rules that have nothing to do with weather: a flue may not be smaller than the appliance connector, and an open fireplace needs a flue of a set share of its opening.
What goes in, and where to measure it
- Appliance - wood stove, open masonry fireplace, oil furnace or boiler, or a gas appliance with a draft hood. It sets the target range and a typical flue gas temperature.
- Chimney height - feet from the appliance outlet (the flue collar) to the top of the chimney, not from the floor and not from the roof.
- Flue size - the inside of the flue: a round liner from 5 to 12 in., or a clay tile of 8-1/2 x 8-1/2, 8-1/2 x 13 or 13 x 13 in. outside dimensions.
- Elbows (wood stove) - 90 degree turns in the stovepipe and chimney. Each one is counted as about 5 ft of lost height.
- Outdoor temperature - check a mild day too. Draft is weakest when the air outside is warm.
- Optional - average flue gas temperature if you have measured it, elevation above sea level, the appliance connector diameter, and for a fireplace the opening width and height.
A short chimney with an elbow, then the same stove three feet taller
A wood stove, 6 in. round flue, 40 F outside, one 90 degree elbow where the pipe turns into the wall. Only the height changes.
Effective height 9 ft. Theoretical draft 0.058 in. w.c. (14.3 Pa). The number clears 0.05, but the effective height is under the 12-16 ft stove manuals ask for, so the verdict is "too short for most stoves".
Effective height 13 ft. Theoretical draft 0.083 in. w.c. (20.7 Pa), inside the stated range and past the minimum height. Taking the elbow out of the 14 ft chimney instead gives 0.090 in. w.c.
Why judge the height and not only the draft figure? Because the equation describes a chimney full of evenly hot gas with no friction. On a short run the gas cools fast and the start-up fire has almost nothing to work with, which is when rooms fill with smoke. The manuals' 12-16 ft rule is the practical floor that theory alone does not show.
Where the draft comes from
Draft is a weight difference. A column of hot flue gas is lighter than a column of outdoor air of the same height, and the difference pushes air into the firebox and gas up the flue. The calculator uses the stack equation dP = 0.0342 x a x h x (1/To - 1/Ti), with atmospheric pressure a in pascals, height h in meters and both temperatures in kelvins, then divides by 249.089 to get inches of water column. Three things follow:
Height scales the draft one to one: double the chimney and the theoretical draft doubles. Weather matters a lot: the same 15 ft wood stove chimney gives 0.116 in. w.c. at 0 F and 0.077 at 85 F. And altitude takes its share, because thinner air weighs less: 0.100 at sea level, 0.082 at 5,280 ft and 0.074 at 8,000 ft for the same chimney at 32 F.
Flue size does not enter the static equation at all. It matters for how much gas the flue can carry and how fast it cools, which is why the result checks it against the connector and the fireplace opening rather than folding it into the draft number.
Wood stove draft by chimney height, cold day and warm day
Straight chimneys, no elbows, flue gas averaging 400 F, sea level. Below 12 ft the verdict flags the height even where the figure looks fine.
| Chimney height | At 20 F | At 70 F | Note |
|---|---|---|---|
| 10 ft | 0.070 in. (17.5 Pa) | 0.055 in. (13.8 Pa) | under the 12 ft floor |
| 12 ft | 0.084 in. (21.0 Pa) | 0.066 in. (16.5 Pa) | lowest height some manuals accept |
| 15 ft | 0.106 in. (26.3 Pa) | 0.083 in. (20.7 Pa) | the most common manual figure |
| 20 ft | 0.141 in. (35.0 Pa) | 0.111 in. (27.6 Pa) | two-story house |
| 25 ft | 0.176 in. (43.8 Pa) | 0.138 in. (34.4 Pa) | stove in a basement |
| 30 ft | 0.211 in. (52.6 Pa) | 0.166 in. (41.3 Pa) | check for overfiring with a gauge |
A cooler fire moves every row down. The same 15 ft chimney at 40 F gives 0.078 in. w.c. with flue gas averaging 300 F and 0.121 at 600 F, which is one reason a smoldering overnight burn drafts poorly and builds creosote.
The ranges the verdict is built on
These are the published figures the result compares against. They describe a gauge reading on a hot, working appliance, so the theoretical number should sit comfortably above the low end. The appliance's own manual or rating plate always overrides them.
| Appliance | Target, in. w.c. | Typical flue gas used | Where the figure comes from |
|---|---|---|---|
| Wood stove | 0.05-0.07; under 0.03 trouble, over 0.10 overfiring | 400 F | Drolet and Osburn owner's manuals |
| Oil furnace or boiler | 0.04-0.06 in the breech; about 0.02 counts as low | 400 F | InspectAPedia oil draft guidance; burner manual governs |
| Gas appliance with a draft hood | about 0.02 | 250 F (diluted at the hood) | HVAC trade practice; rating plate governs |
| Open masonry fireplace | no gauge figure; flue at least 1/10 (square or rectangular) or 1/12 (round) of the opening on chimneys of 15 ft or more | 300 F | International Residential Code, flue area for fireplaces |
The typical temperatures are an average along the chimney, not a reading at the collar, and they are assumptions. If you have measured your flue gas, type it in and the calculator uses it instead. A 36 x 24 in. fireplace opening is 864 sq in, so it needs 86.4 sq in of rectangular flue or 72 sq in of round: a 13 x 13 in. tile or a 10 in. round liner, while an 8-1/2 x 13 in. tile at 74 sq in falls short.
What stays the same however tall the chimney is
The roof rule does not care about draft. A masonry chimney must rise at least 3 ft above the point where it passes through the roof and at least 2 ft above any part of the building within 10 ft measured horizontally, the 3-2-10 rule. On a steep roof the 10 ft part usually sets the height. Factory-built chimneys follow the manufacturer's listed installation instructions.
Draft questions people ask before lighting up
Related tools
Heat Loss Calculator
Btu/hr lost through walls, windows, attic, floor and air leakage at the design temperature - See the calculator
Baseboard Heat Calculator
Feet of hot water or electric baseboard for a room from its heat loss - See the calculator
Roof Pitch Calculator
Pitch, degrees and percent, handy when working out the 10 ft clearance on a sloped roof - See the calculator
Brick & Mortar Calculator
Bricks and mortar for a masonry chimney stack or a hearth - See the calculator
Insulation Calculator
Insulation for the walls and attic the chimney passes through - See the calculator
Roof Calculator
Roof area and shingles, including the cut-out around a chimney - See the calculator
Gas vs Electric Heating Calculator
Running cost of a gas appliance against electric heat - See the calculator
Heat Pump COP Calculator
Efficiency of a heat pump, the option that needs no chimney at all - See the calculator