Heat Loss Calculator - Btu/hr for a Room or House

    Walls, windows, attic, floor and air leakage in; design heat loss in Btu per hour out, split line by line so you can see which upgrade cuts the most before sizing a furnace or heat pump.

    Parameters

    Enter data for calculations

    Heated area

    Floor to ceiling

    Walls facing outdoors

    Empty = no windows

    Empty = no doors

    Whole-assembly U-factor

    Or type the label U-factor

    Empty = use the type above

    Empty = 2 in. wood

    Attic, roof or another floor

    Crawlspace, slab or another floor

    Air changes per hour

    Empty = 70 F

    Local heating design value

    Form progress0 / 8 fields

    💡 Fill in all required fields to unlock the calculate button

    Heat loss in Btu per hour, line by line

    Describe the walls, windows, ceiling, floor and air leakage of a room or a whole house, set the indoor and outdoor design temperatures, and this heat loss calculator adds up how many Btu per hour escape on the coldest design day. It shows which surface loses the most, so you can see whether a furnace upgrade, new windows or attic insulation buys more.

    Quick start: a 1,500 sq ft one-story house, 8 ft ceilings, 160 ft of outside wall, 2x4 walls with batts, 180 sq ft of clear double-pane windows, two doors (40 sq ft), R-30 attic, floor over an unheated crawlspace, average airtightness (0.5 air changes per hour), 70 F inside and 5 F outside. Result: 27,100 Btu/hr, which is 18.1 Btu/hr per sq ft or 7.94 kW.

    Measuring up before you start

    1. Floor area and ceiling height - heated square feet and the height in feet. Together they give the air volume for the leakage line.
    2. Outside wall length - feet of wall that faces outdoors. For a whole rectangular house this is the perimeter; for one room, only its outside walls. On a slab it is also the slab edge.
    3. Windows and doors - glass area in square feet (a 3 x 5 ft window is 15 sq ft) and door area (a standard 3 x 6.7 ft door is about 20 sq ft). If the window label lists an NFRC U-factor, type it in.
    4. Wall, ceiling and floor - pick the closest construction. Each choice carries a published U-factor, shown in the result.
    5. Airtightness - 0.35, 0.5, 1 or 1.5 air changes per hour, from a tight new house to a drafty old one. A blower door test gives the real figure.
    6. Design temperatures - indoor (empty = 70 F) and the outdoor heating design temperature for your area, the cold your system should handle, not the record low.

    Where the 27,100 Btu/hr in the quick start goes

    The table splits the example house into the six lines the result shows. The leakage line is the largest, and the windows lose more than the walls despite having a sixth of their area.

    LineArithmetic (65 F difference)Btu/hr
    Walls0.067 x 1,060 sq ft net x 654,616
    Windows0.53 x 180 x 656,201
    Doors0.45 x 40 x 651,170
    Ceiling0.036 x 1,500 x 653,510
    Floor0.047 x 1,500 x 654,583
    Air leakage0.018 x 0.5 x 12,000 cu ft x 657,020

    Ten houses and rooms run through the calculator

    Unless a line says otherwise, each one is the quick start house with a single change, so you can read off what that change is worth.

    Colder design day, -15 F

    35,438 Btu/hr. Heat loss rises in a straight line with the temperature difference.

    Mild climate, 25 F

    18,761 Btu/hr for the same house.

    Windows replaced, U-0.30

    24,409 Btu/hr, about 2,700 less.

    Attic to U-0.024

    25,930 Btu/hr: the R-30 attic was already decent, so the gain is 1,170.

    Leakier, 1 air change per hour

    34,120 Btu/hr, 7,020 more than the quick start.

    Walls with no insulation

    36,264 Btu/hr: empty 2x4 cavities triple the wall line.

    Old house at -10 F

    Uninsulated walls, single-pane wood windows, R-19 attic, slab, 1.5 air changes: 71,496 Btu/hr, 47.7 per sq ft.

    Tight new house at -5 F

    2x6 with board, low-e gas-filled glass, attic and floor at IECC levels, 0.35 air changes: 19,940 Btu/hr, 13.3 per sq ft.

    Corner bedroom, 180 sq ft

    27 ft of 2x6 outside wall, 24 sq ft of low-e glass, heated rooms above and below, 10 F: 1,734 Btu/hr.

    Uninsulated garage kept at 55 F

    400 sq ft, 60 ft of bare 2x4 wall, bare roof deck, slab, 1.5 air changes, 10 F outside: 19,179 Btu/hr.

    The U-factors behind each choice

    A U-factor is the heat in Btu per hour that passes through one square foot for each degree F of difference, so lower is better and U = 1 / R for a whole assembly. These are the values the form uses, with the source for each group.

    PartChoices and U-factorSource
    Walls2x4 bare 0.20; 2x4 batts 0.067; plus 1 in. foam 0.056; 2x6 batts 0.043; 2x6 with board 0.036Engineering ToolBox stud wall R-values
    Windowssingle wood frame 0.83; single metal 1.02; clear double 0.53; low-e 0.32; low-e with gas 0.27; code maximum 0.30Engineering ToolBox; IECC zones 3-8
    Doorsmetal sheet 1.2; 1 in. wood 0.65; 2 in. wood 0.45Engineering ToolBox
    Ceilingbare roof deck 0.5; attic R-19 0.049; R-30 0.036; code zones 2-3 0.026; zones 4-8 0.024Engineering ToolBox; Seattle Energy Code defaults; IECC
    Floorover unheated space 0.047 (zones 3-4) or 0.033 (zones 5-6); uninsulated slab F-0.73 per foot of edgeIECC; ASHRAE 90.1 slab table

    Slabs lose most of their heat at the edge, so they are counted per foot of exposed perimeter, not per square foot. Air leakage uses 0.018 Btu per cubic foot per degree, the heat it takes to warm a cubic foot of air by one degree.

    From Btu per hour to a heating system

    The total is what the heating system must replace at the design temperature, so it is the starting point for a furnace, boiler, heat pump or baseboard size. Run it room by room to size radiators or baseboard, and for the whole house to size the central unit. A furnace rated by input loses part of it up the flue: a 90% furnace with a 30,000 Btu/hr output needs about 33,300 Btu/hr of input. Contractors confirm sizes with ACCA Manual J, which adds duct losses and treats each room separately.

    Heat loss questions from homeowners

    How many Btu do I need to heat a 1,500 sq ft house?

    It depends on the envelope and the climate far more than on the floor area. The ten cases above run from 13.3 to 47.7 Btu/hr per sq ft, which for 1,500 sq ft is roughly 20,000 to 71,500 Btu/hr. A rule of thumb per square foot cannot see that range.

    What outdoor temperature should I use?

    The local heating design temperature, the cold that is reached or beaten only a small share of the hours in a typical winter. It is listed in ACCA Manual J and ASHRAE climate tables and is warmer than the record low. Using the record low oversizes the system.

    How do I turn an R-value into a U-factor?

    U = 1 / R for the whole assembly, framing and air films included. An R-15 wall assembly is U-0.067. The R printed on a batt covers the insulation only, and the studs between the batts lower the real figure, so pick the closest assembly in the list rather than dividing 1 by the batt label.

    Why is air leakage such a large line?

    Because every cubic foot of cold air that slips in has to be warmed to room temperature. In the quick start house, half an air change per hour is 6,000 cubic feet an hour and 7,020 Btu/hr, more than any single surface. At one air change per hour it doubles.

    Can I use this for a garage or a basement?

    For a garage, yes: set the indoor temperature you want to hold (for example 55 F) and pick the bare constructions. For basement walls below grade the ground is warmer than the air, so these above-grade values overstate the loss; treat the result as an upper bound.

    Related tools

    Baseboard Heat Calculator

    Feet of hot water or electric baseboard for a room from its heat loss - See the calculator

    Chimney Draft Calculator

    Draft in inches of water column for a wood stove, fireplace, oil or gas flue - See the calculator

    Insulation Calculator

    How much insulation the walls or attic need - See the calculator

    Air Conditioner Size Calculator

    The cooling side of the same house, in Btu and tons - See the calculator

    Gas vs Electric Heating Calculator

    What the heat loss costs to replace with gas or electricity - See the calculator

    Heat Pump COP Calculator

    Efficiency of a heat pump at a given outdoor temperature - See the calculator

    Gas Bill Calculator

    Monthly gas cost from usage and rates - See the calculator

    House Building Cost Calculator

    Budget for a new build, insulation and windows included - See the calculator

    Similar calculators from this section