Radiant Floor Heating Calculator - Btu, PEX and Loops

    Turn a room heat loss into Btu per square foot and a floor surface temperature, checked against the 85 F limit, then into feet of PEX, circuits and gpm for the spacing you pick.

    Parameters

    Enter data for calculations

    At the design temperature

    Length x width

    Empty = 0

    Empty = 68 F

    Comfort and covering

    Or type the R-value

    Empty = use the list

    Center to center

    Nominal size

    Empty = 20 F

    Form progress0 / 5 fields

    💡 Fill in all required fields to unlock the calculate button

    Radiant floor heating: Btu per square foot, floor temperature and PEX

    A room that loses 4,000 Btu/hr through 180 sq ft of tubed floor needs 22.2 Btu/hr from every square foot, which puts a tiled surface at 79.7 F in a 68 F room. This radiant floor heating calculator does that arithmetic for any room, checks it against the floor temperature limit, and turns the tubed area into feet of PEX, circuits and gallons per minute.

    Six answers the form needs

    1. Heat loss of the room - Btu/hr at the design temperature, from a Manual J report or the heat loss calculator linked below.
    2. Floor area and area without tubing - square feet of the room, then the part under cabinets, a tub or a shower base where no tubing goes.
    3. Floor surface limit - 85 F is the manufacturer maximum for all floors; CSA B214 allows 88 F in living space, 91 F in bathrooms and 95 F along outside walls.
    4. Room temperature - empty means 68 F, the air temperature the circuit length table assumes.
    5. Floor covering - pick one from the list, or type the combined R-value of the covering and its pad or underlayment.
    6. Tubing spacing, size and temperature drop - 6, 8, 9 or 12 in. on center, 3/8 to 3/4 in. PEX, and a 10, 15 or 20 F drop (empty means 20 F).

    The four constants behind every result

    1.9

    Btu/hr per sq ft for each degree the floor runs above the room

    85 F

    recommended maximum floor surface, hardwood included

    20 F

    the traditional design drop from supply to return

    +10%

    tubing added for the leaders back to the manifold

    All four come from the Viega radiant heating design manual; the surface limits for bathrooms and perimeter strips are quoted there from CSA B214 Clause 14.2.1. The flow follows the manual's equation, Btu/hr divided by (temperature drop x 8.01 x 62.4) for plain water.

    How much a floor can give at each limit

    Multiply 1.9 by the gap between the surface limit and a 68 F room. If the room needs more than this per square foot of tubed floor, the floor cannot carry it alone, whatever the water temperature.

    Surface limitWhere it appliesMax output at 68 F
    85 FViega recommendation, all floors32.3 Btu/hr/sq ft
    88 FCSA B214, dwellings and commercial space38.0 Btu/hr/sq ft
    91 FCSA B214, bathrooms, indoor pools, foyers43.7 Btu/hr/sq ft
    95 FCSA B214, perimeter strip up to 2.5 ft from outside walls51.3 Btu/hr/sq ft

    Floor coverings, from tile to thick carpet

    The covering does not change what the room gets from a floor at a given surface temperature. It changes how hot the slab or panel underneath has to be to keep that surface temperature. The R-values are from the manual's table of coverings; the last column is the room from the opening paragraph, 22.2 Btu/hr per sq ft with the surface at 79.7 F.

    CoveringR-valueSlab or panel top
    Bare concrete or gypsum topping079.7 F
    Ceramic tile 3/8 in., or vinyl 1/8 in.0.0580.8 F
    Laminated parquet 3/8 in.0.3487.3 F
    Maple 3/4 in.0.7897.0 F
    Oak 3/4 in.0.9099.7 F
    Nylon plush 1/2 in. on waffled rubber pad 3/8 in.1.65116.4 F
    Nylon plush 1/2 in. on prime urethane pad 1/2 in.3.19150.6 F

    The same manual caps supply water at 140 F for thin slabs and tile and 150 F for concrete, so the thick-pad carpet row already needs the top of the slab hotter than a concrete system is allowed to run on its supply. A thinner, denser pad is the usual fix.

    PEX per square foot and circuit lengths

    Feet of tubing per square foot of tubed floor is 12 divided by the spacing in inches, plus 10% for leaders. The longest circuit drops by 50 ft once a room needs more than 25 Btu/hr per sq ft.

    Spacingft per sq ftTubingMax circuit, up to / over 25 Btu/hr/sq ft
    6 in.2.23/8 in.300 / 250 ft
    8 in.1.651/2 in.400 / 350 ft
    9 in.1.475/8 in.500 / 450 ft
    12 in.1.13/4 in.800 / 750 ft

    The circuit lengths are Viega's for a drop of at least 20 F, plain water and 68 F air. CSA B214 sets shorter defaults (for example 300 ft for 1/2 in.) that apply only when the tubing maker gives no figure, so check the manual of the PEX you buy.

    Patterns that show up across rooms

    Spacing changes tubing, not output. In this model the room still needs 22.2 Btu/hr per sq ft at 6 or 12 in.; closer tubing buys a lower water temperature, at the price of 396 ft of PEX instead of 198 ft for the opening room.

    Bathrooms hit the limit first. A small room with an outside wall and a tub can need more than the floor gives. An 80 sq ft bathroom losing 3,000 Btu/hr with 15 sq ft under the tub and vanity needs 46.2 Btu/hr per sq ft; even at the 91 F bathroom limit and 72 F inside it falls 654 Btu/hr short.

    A whole house splits into circuits. The 1,500 sq ft house from the heat loss calculator (27,100 Btu/hr) with 150 sq ft left untubed needs 20.1 Btu/hr per sq ft, 1,980 ft of 1/2 in. PEX at 9 in. and 5 circuits at about 2.71 gpm in all.

    Halving the temperature drop doubles the flow. A basement slab of 900 tubed sq ft at 20,000 Btu/hr needs 4.00 gpm at a 10 F drop and 2.00 gpm at 20 F.

    Radiant floor questions

    How many Btu per square foot can radiant floor heat put out?

    About 32 Btu/hr per sq ft in a 68 F room with the floor at the 85 F maximum, from 1.9 x 17. Allowing 88 F raises it to 38; a perimeter strip at 95 F gives 51.

    How much PEX do I need for radiant floor heat?

    Tubed square feet times 12 divided by the spacing, plus about 10% for leaders: 1.47 ft per sq ft at 9 in., 2.2 ft at 6 in. A 300 sq ft room at 9 in. needs about 440 ft.

    What size PEX for radiant floor heat?

    The manual's typical choice for slabs in living areas is 1/2 or 5/8 in. at 9 in. on center, and 3/8 or 1/2 in. at 6 to 9 in. in bathrooms and high-output areas. Larger tubing mainly lets one circuit run longer.

    Why does the calculator not give the water temperature?

    Because it depends on the whole build-up: slab thickness, plates or panels, spacing and the covering. Manufacturers publish charts for each assembly. The result gives the temperature the top of the slab or panel must reach, which is the starting point for reading those charts.

    Should I leave the area under cabinets and the tub untubed?

    Enter it as area without tubing. The room's heat then has to come from fewer square feet, so the floor runs warmer, which is why kitchens and bathrooms reach the limit sooner than their size suggests.

    Does this cover electric floor heating mats?

    The output and surface temperature lines do, since 1 W is 3.412 Btu/hr. The tubing, circuits and flow are for hydronic systems only.

    Related tools

    HRV Sizing Calculator

    Balanced cfm for an HRV or ERV under the IRC or ASHRAE 62.2 - See the calculator

    Heat Loss Calculator

    The room heat loss in Btu/hr that this calculator starts from - See the calculator

    Baseboard Heat Calculator

    Hot water or electric baseboard for rooms the floor cannot carry - See the calculator

    Flooring Calculator

    How much flooring the room needs, waste included - See the calculator

    Tile Calculator

    Tiles, boxes and grout for a floor - See the calculator

    Insulation Calculator

    Insulation under the slab or between the joists - See the calculator

    Heat Pump COP Calculator

    Efficiency of a heat pump at a given outdoor temperature - See the calculator

    Similar calculators from this section