Voltage Drop Calculator - Wire Gauge for Long Runs

    Voltage drop over a long run, turned into a wire gauge: copper or aluminum, AWG to 500 kcmil, 120 to 480 V or DC, with the volts left at the load and the longest run each size allows.

    Parameters

    Enter data for calculations

    A gauge, or a check of yours

    Single-phase, three-phase or DC

    Nominal supply voltage

    In the unit chosen next

    Amps or watts

    Panel to load, not the total wire

    Feet or meters

    Copper or aluminum

    How much voltage you accept losing

    Form progress0 / 9 fields

    💡 Fill in all required fields to unlock the calculate button

    Voltage drop and the wire gauge that keeps it in check

    A 16 A load at the end of 100 ft of 12 AWG copper sees 113.66 V instead of 120. That is a 5.28% drop, and 12 AWG is the gauge most people would pick for a 20 A circuit. This calculator finds the smallest copper or aluminum gauge that keeps the drop under the limit you choose and still carries the current, or checks a gauge you already own. For that same run it answers 8 AWG, with a drop of 2.07%.

    It works for single-phase and three-phase AC and for DC, takes the load in amps or watts and the length in feet or meters, and lists the sizes on either side so you can see what one step up or down would do.

    The nine boxes, from supply to limit

    1. What you want - a suggested gauge, or a check of the gauge you already have.
    2. Supply - single-phase AC (a 120 V or 240 V house circuit), three-phase AC (208 V or 480 V commercial), or DC (12 V, 24 V or 48 V battery and solar wiring).
    3. Voltage - the nominal supply voltage, for example 120, 240, 208, 480 or 12.
    4. Load and its unit - the current in amps from the nameplate, or the power in watts.
    5. Power factor - only for a load in watts on AC: 1 for heaters and incandescent lamps, about 0.8 to 0.9 for motors.
    6. Length and its unit - the one-way distance from the panel to the load, not the total length of wire.
    7. Conductor - copper or aluminum.
    8. Voltage drop limit - 3% for a branch circuit is the usual choice, 5% for a less sensitive load, 1% or 2% for low-voltage lighting and electronics.
    9. Read the result - the gauge, the drop in volts and percent, the voltage left at the load, the heat in the wire and the longest run that gauge allows.

    Sizing a run in four moves

    Under the form, the calculator does the same four things an electrician does on paper. Here they are for a 40 A EV charger circuit, 240 V, 120 ft of copper, 3% limit.

    1
    Turn the limit into volts.
    3% of 240 V is 7.2 V. That is the whole budget for the wire out and the wire back.
    2
    Find the most resistance you can afford.
    R = 7.2 x 1,000 / (2 x 40 x 120) = 0.75 ohm per 1,000 ft. The 2 is there because the current travels both ways.
    3
    Pick the first gauge under that figure.
    8 AWG copper is 0.778, just over. 6 AWG is 0.491, so 6 AWG it is: 4.71 V, or 1.96%.
    4
    Check it can carry the current.
    6 AWG copper has a usable ampacity of 55 A, above 40 A, so both checks agree. On a shorter run the ampacity check is usually the one that wins.

    Copper against aluminum on one 150 ft feeder

    The same load, 50 A at 240 V over 150 ft with a 3% limit, sized in both metals. Aluminum needs one size larger here and runs a little warmer, which is the usual trade for a cheaper, lighter cable.

    What you get Copper Aluminum Who should choose it
    Smallest gauge that passes4 AWG3 AWGAluminum if the conduit has room for one size up
    Resistance, ohm per 1,000 ft0.3080.403From NEC Chapter 9, Table 8
    Voltage drop4.62 V (1.93%)6.05 V (2.52%)Copper for motors that start hard
    Heat in the wire231 W302 WCopper for loads that run all day
    Usable ampacity70 A65 ABoth leave headroom over 50 A
    Longest run at 3%233 ft178 ftCopper if the load may move farther later
    VerdictBoth pass; aluminum costs one gaugeTerminals must be rated AL/CU

    The formula, and three runs checked against it

    Voltage drop is Ohm's law applied to the wire itself: VD = k x I x R x L / 1,000, with I in amps, R in ohms per 1,000 ft and L the one-way length in feet. On single-phase and DC, k = 2, because the current flows out on one conductor and back on the other. On a balanced three-phase circuit, k = 1.732, the square root of 3.

    Workshop outlet, 16 A at 120 V, 100 ft, copper, 3%.
    12 AWG: 2 x 16 x 1.98 x 100 / 1,000 = 6.34 V, which is 5.28%. 10 AWG gives 3.31%, still over. 8 AWG: 2.49 V, 2.07%, with 117.51 V left at the tool. Distance decided it.
    Three-phase motor feeder, 100 A at 480 V, 300 ft, copper, 3%.
    3 AWG would already keep the drop under 3%, but its usable ampacity is 85 A. 1 AWG carries 110 A and drops 1.732 x 100 x 0.154 x 300 / 1,000 = 8.00 V, 1.67%. Current decided it.
    12 V DC pump, 10 A, 20 ft from the battery, copper, 3%.
    The budget is only 0.36 V. 14 AWG would drop 10.47%. 8 AWG: 2 x 10 x 0.778 x 20 / 1,000 = 0.31 V, 2.59%. Low voltage is where distance hurts most.

    How far each copper gauge reaches at 15 A

    Longest one-way run before the drop passes 3% with a 15 A load. Doubling the voltage doubles the reach, because the same volts lost become half the percentage. For other currents, scale inversely: twice the amps, half the distance.

    Copper gauge Ohm per 1,000 ft Usable ampacity 120 V, 15 A 240 V, 15 A
    14 AWG3.1415 A38 ft76 ft
    12 AWG1.9820 A60 ft121 ft
    10 AWG1.2430 A96 ft193 ft
    8 AWG0.77840 A154 ft308 ft
    6 AWG0.49155 A244 ft488 ft
    4 AWG0.30870 A389 ft779 ft
    2 AWG0.19495 A618 ft1,237 ft
    1/0 AWG0.122150 A983 ft1,967 ft

    Usable ampacity is the Table 310.16 figure you can actually load the wire to: the 60 °C column up to 1 AWG and the 75 °C column from 1/0, with the 15, 20 and 30 A limits NEC 240.4(D) puts on 14, 12 and 10 AWG copper.

    Four mistakes that shrink the wire too far

    Entering the total wire length. The length box wants the one-way distance. Typing 200 ft for a run that is 100 ft away doubles the answer a second time, because the formula already counts the return conductor.
    Sizing for ampacity alone. 12 AWG is fine for 16 A over 30 ft. Over 100 ft at 120 V it drops 5.28%, and a motor on the end starts slowly and runs hot.
    Using the 90 °C column. The insulation may be rated 90 °C, but the breaker and receptacle terminals rarely are. NEC 110.14(C) holds most circuits to the 60 °C or 75 °C figures, which is what the calculator uses.
    Forgetting continuous loads. A load that runs three hours or more, such as an EV charger or a water heater, is sized at 125% of its current. Enter 50 A for a 40 A charger if you are sizing for the breaker too.

    Voltage drop questions from real runs

    Is the 3% voltage drop limit required by code?
    No. The 3% for a branch circuit and 5% for feeder plus branch appear as an informational note in NEC 210.19(A), which is advice rather than a rule. Some cities and states adopt them as mandatory amendments, and a few equipment makers require them for the warranty, so check locally.
    What size wire for 100 ft at 20 A on 120 V?
    At a 3% limit, 8 AWG copper: 2 x 20 x 0.778 x 100 / 1,000 = 3.11 V, or 2.59%. 10 AWG would drop 4.13%. If you want margin, 6 AWG brings it down to 1.96 V, 1.64%, and the table under the result shows both.
    Why does 240 V reach so much farther than 120 V?
    At the same current the wire loses the same number of volts, but 3% of 240 V is 7.2 V against 3.6 V at 120 V, so the reach doubles. For the same wattage it goes further still, because 240 V draws half the current: a 1,800 W heater on 12 AWG reaches 60 ft at 120 V and 242 ft at 240 V, four times as far.
    Does this include the neutral on a three-phase circuit?
    On a balanced three-phase load the neutral carries almost no current, so the drop is line to line with the factor 1.732. For a single-phase load connected line to neutral on a three-phase system, choose single-phase and enter the line-to-neutral voltage, for example 120 V or 277 V.
    Why is there no 14 AWG aluminum?
    Table 310.16 gives no ampacity for 14 AWG aluminum, and building wire in aluminum starts at 12 AWG. In practice aluminum is used for feeders of 6 AWG and larger, where its lower price per ampere pays for the bigger size.
    How accurate is it on very large wire?
    The calculator uses DC resistance at 75 °C and leaves out reactance. Up to about 1/0 that changes the answer very little. On 250 kcmil and larger in steel conduit, with a motor load at a low power factor, the real drop can be several percent higher, and NEC Chapter 9, Table 9 is the reference to use.

    Related tools

    Doppler Effect Calculator

    Frequency shifts of sound, radar and light, and the speed behind a measured shift - See calculator

    Punch Force Calculator

    Peak force of a punch in newtons from hand speed, effective mass and contact time - See calculator

    Amps Calculator

    Turns watts into amps and shows the breaker and wire for a short run - See calculator

    Electrical Power Calculator

    Watts, VA and kWh from any two electrical readings - See calculator

    Ohm's Law Calculator

    Voltage, current and resistance, the relation behind every voltage drop - See calculator

    Transformer Calculator

    Turns ratio and full-load current, for runs fed from a step-down transformer - See calculator

    Electric Motor Efficiency Calculator

    What a motor turns into shaft power once the supply reaches it - See calculator

    Battery Life Calculator

    Runtime of a 12 V or 24 V battery, where every volt lost in the cable matters - See calculator

    Electrical Cable Length Calculator

    How much cable to buy for a room once the gauge is settled - See calculator

    Ready-made calculations

    The most searched variants of this calculator. Each link opens it with the value already filled in, ready to calculate.

    Similar calculators from this section