Find the secondary voltage, turns or turns ratio of a transformer, then the full-load amps on both sides from its VA or kVA rating, for single-phase or three-phase supplies.
Transformer Calculator - Turns Ratio, Voltage, kVA to Amps
Find the secondary voltage, turns or turns ratio of a transformer, then the full-load amps on both sides from its VA or kVA rating, for single-phase or three-phase supplies.
Parameters
Enter data for calculations
💡 Fill in all required fields to unlock the calculate button
A transformer calculator built around one ratio
Wind 500 turns on one side of a core and 100 on the other, feed it 120 V, and 24 V comes out: the voltages follow the turns, and the currents go the opposite way. This tool solves that ratio for whichever number is missing, the secondary or primary voltage, the secondary or primary turns, or just the turns ratio from two voltages. Add the VA or kVA rating and it gives the full-load current on both sides, single-phase or three-phase, with the losses if you know the efficiency.
What each field expects
- What to find - secondary voltage, primary voltage, secondary turns, primary turns, or the turns ratio from two voltages when the turn counts are unknown, which is the usual case with a bought transformer.
- Primary and secondary voltage - RMS values from the nameplate, such as 120 V in and 24 V out. For three-phase use line-to-line voltages, for example 480 V and 208 V.
- Primary and secondary turns - only for the turn modes. When the answer is not a whole number, the result also shows what the nearest whole turn counts would really give.
- Rating and its unit (optional) - VA for small transformers, kVA for building and utility units.
- Phases - needed with a rating, because the current formula differs: S ÷ V for single-phase, S ÷ (√3 × V) for three-phase.
- Efficiency (optional) - in percent. Without it the primary current is the ideal one, with no losses.
- Read the result - the answer in the colored box, both voltages, the turns and the ratio, then the currents and losses when a rating was entered.
Everything the ratio decides
Both windings share the same changing magnetic flux, so each turn has the same voltage induced in it. That is the whole reason V1 ÷ V2 = N1 ÷ N2: a winding with five times as many turns carries five times the voltage. Power in has to equal power out in an ideal transformer, so the current does the reverse. A 5 : 1 step-down that delivers 1.667 A at 24 V draws only a fifth of that, 333.3 mA, from the 120 V side.
There is a third quantity the ratio controls, less often mentioned. A resistance hung on the secondary looks, from the primary, like that resistance multiplied by the square of the turns ratio. An 8 Ω speaker behind a 10 : 1 output transformer appears as 800 Ω to the amplifier tube driving it. Matching those impedances is what audio output transformers are for.
A transformer's rating is apparent power in volt-amperes, not watts. The windings heat up with current whatever the power factor of the load, so the nameplate limits VA. On a resistive load such as a heater or an incandescent bulb, VA and watts are the same number.
Full-load current for common kVA ratings
These are the currents each rating allows at full load, rounded to two decimals, from I = S ÷ V for single-phase and I = S ÷ (√3 × V) for three-phase. The calculator gives the same figures for any rating you type.
| Rating | Single-phase 240 V | Single-phase 120 V | Three-phase 480 V | Three-phase 208 V |
|---|---|---|---|---|
| 15 kVA | 62.50 A | 125.00 A | 18.04 A | 41.64 A |
| 25 kVA | 104.17 A | 208.33 A | 30.07 A | 69.39 A |
| 45 kVA | 187.50 A | 375.00 A | 54.13 A | 124.91 A |
| 75 kVA | 312.50 A | 625.00 A | 90.21 A | 208.18 A |
| 150 kVA | 625.00 A | 1,250.00 A | 180.42 A | 416.36 A |
| 300 kVA | 1,250.00 A | 2,500.00 A | 360.84 A | 832.72 A |
The three-phase columns are why a 75 kVA unit is a common size for a small commercial building: at 208 V it supplies a little over 200 A per line. The breaker and conductors for that current are a separate question, sized by the electrical code rather than by this arithmetic.
Transformers around a North American house
The ratios below are the nameplate voltages divided, which is what the calculator's ratio mode returns. Real turn counts are a little different, because manufacturers add turns to the secondary to make up for the voltage drop under load.
| Where | Voltages | Ratio |
|---|---|---|
| Utility transformer on the pole | 7,200 V to 240 V | 30 : 1 |
| Furnace or air conditioner controls | 120 V to 24 V | 5 : 1 |
| Doorbell | 120 V to 16 V | 7.5 : 1 |
| Low-voltage landscape lighting | 120 V to 12 V | 10 : 1 |
| Tube amplifier heater winding | 120 V to 6.3 V | 19.0476 : 1 |
| Step-up for 240 V equipment on a 120 V outlet | 120 V to 240 V | 1 : 2 |
Five transformer facts that catch people out
People who end up here, and what they type
Quick questions about ratios, VA and turns
Related tools
Capacitor Energy Calculator
Joules and Wh stored in the filter capacitor after a transformer and rectifier - Open the calculator
Battery Life Calculator
How long a battery runs a load, with depth of discharge and inverter losses - Open the calculator
Amps Calculator
Watts to amps with the breaker and wire size for the circuit feeding the primary - Open the calculator
Electrical Power Calculator
Real, apparent and reactive power, the difference between VA and watts - Open the calculator
Ohm's Law Calculator
Current through a resistive load hung on the secondary - Open the calculator
Thermal Efficiency Calculator
The same useful-out over total-in idea applied to heaters and engines - Open the calculator