Convert watts to amps for DC, single-phase or three-phase AC, or find amps from volts and ohms, then see the smallest standard breaker and copper wire gauge for the load.
How many amps is 800 watts at 120 volts?
Convert watts to amps for DC, single-phase or three-phase AC, or find amps from volts and ohms, then see the smallest standard breaker and copper wire gauge for the load.
The calculator below is set to 800 watts on a 120 V circuit, in the watts and volts mode, with the power entered in watts. That mode treats the load as resistive, with a power factor of 1, the way a space heater, a toaster or an incandescent bulb behaves, so the current is 800 divided by 120.
Under the current the result lists the smallest standard breaker and the smallest copper wire gauge twice: once for a load that runs under three hours at a time, and once for a continuous load of three hours or more, which the National Electrical Code sizes at 125 %. Motors and many power supplies draw more current than watts divided by volts suggests, so for those switch to the single-phase AC mode and enter the power factor from the nameplate.
Parameters
Enter data for calculations
💡 Fill in all required fields to unlock the calculate button
Amps, breakers and wire gauge on one page
How many amps does a 1,500 W heater draw on a 120 V outlet? 12.5 A. The calculator gets current from watts and volts, from volts and ohms, or from watts and ohms, and on AC it takes the power factor and the three-phase √3 into account. Every answer comes with the smallest standard breaker and the smallest copper wire that cover it, once for an ordinary load and once for a load that runs three hours or more.
Filling in the calculator
- What you know - watts and volts (DC or a resistive load), watts, volts and power factor on single-phase AC, the same on three-phase AC, volts and ohms, or watts and ohms.
- Power and its unit - the nameplate rating in W or kW. A 4.8 kW water heater can go in as 4.8 with kW selected.
- Voltage - 120 V or 240 V in a US home, 12 V in a car. On three-phase use the line-to-line voltage, such as 208 V or 480 V.
- Resistance - ohms, for the two modes that use it.
- Power factor - AC modes only, between 0 and 1; 1 for heaters, the nameplate figure for motors.
- Read the result - the current and its formula, the other quantities, and the breaker and wire table for both load types.
What sets the current in a circuit
An ampere is a flow of one coulomb of charge per second. The supply sets the voltage, the load decides how much current it takes at that voltage, and the power is the product of the two. Turn P = V × I around and you get the formula most people want: I = P ÷ V. The same 1,500 W takes 12.5 A at 120 V and only 6.25 A at 240 V, which is why large appliances in North American homes sit on 240 V circuits.
Ohm's law gives the other two routes. With voltage and resistance known, I = V ÷ R. With power and resistance known, I = √(P ÷ R), because P = I² × R. A 100 W load of 4 Ω therefore carries 5 A and sees 20 V.
Alternating current adds two corrections. The power factor is the ratio of real power to apparent power, so a motor with a power factor of 0.8 draws 1 ÷ 0.8 = 1.25 times the current its wattage alone suggests. On a balanced three-phase supply the power is split across three lines and the voltage between two lines is √3 times the voltage of one phase, which gives I = P ÷ (√3 × V × PF).
The breaker side follows the National Electrical Code. Standard breaker ratings are listed in NEC 240.6(A): 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125 A and upward. A load that runs 3 hours or more counts as continuous, and NEC 210.20(A) requires the breaker to be rated for at least 125% of it. The wire then has to carry the breaker rating, with the small-conductor limits of NEC 240.4(D) capping 14, 12 and 10 AWG copper at 15, 20 and 30 A.
Watts to amps at five common supplies
Current for purely resistive loads (power factor 1). The 12 V column is a car or a battery bank, the next two are ordinary US circuits, and the last two are three-phase supplies with line-to-line voltages of 208 V and 480 V. Values are rounded to two decimals.
| Load | 12 V DC | 120 V | 240 V | 208 V three-phase | 480 V three-phase |
|---|---|---|---|---|---|
| 100 W | 8.33 A | 0.83 A | 0.42 A | 0.28 A | 0.12 A |
| 500 W | 41.67 A | 4.17 A | 2.08 A | 1.39 A | 0.6 A |
| 1,000 W | 83.33 A | 8.33 A | 4.17 A | 2.78 A | 1.2 A |
| 1,500 W | 125 A | 12.5 A | 6.25 A | 4.16 A | 1.8 A |
| 3,000 W | 250 A | 25 A | 12.5 A | 8.33 A | 3.61 A |
| 5,000 W | 416.67 A | 41.67 A | 20.83 A | 13.88 A | 6.01 A |
| 10,000 W | 833.33 A | 83.33 A | 41.67 A | 27.76 A | 12.03 A |
Read across a row and the pattern is plain: doubling the voltage halves the current, and three-phase at 480 V carries 10,000 W on 12.03 A per line where a 240 V single-phase circuit needs 41.67 A.
Copper wire gauges and what they may carry
Ampacity is the current a conductor can carry continuously without exceeding its insulation temperature. The figures below are for copper from NEC Table 310.16: no more than three current-carrying conductors in a raceway or cable, 30 °C (86 °F) ambient. Which column applies depends on the insulation and on the temperature rating of the terminals at both ends, and the calculator uses the 60 °C column because it is the conservative one. Diameters and areas are from the American wire gauge definition.
| Gauge | Diameter | Area | 60 °C | 75 °C | 90 °C | Breaker cap, 240.4(D) |
|---|---|---|---|---|---|---|
| 14 AWG | 0.0641 in | 2.08 mm² | 15 A | 20 A | 25 A | 15 A |
| 12 AWG | 0.0808 in | 3.31 mm² | 20 A | 25 A | 30 A | 20 A |
| 10 AWG | 0.1019 in | 5.26 mm² | 30 A | 35 A | 40 A | 30 A |
| 8 AWG | 0.1285 in | 8.37 mm² | 40 A | 50 A | 55 A | - |
| 6 AWG | 0.1620 in | 13.3 mm² | 55 A | 65 A | 75 A | - |
| 4 AWG | 0.2043 in | 21.2 mm² | 70 A | 85 A | 95 A | - |
| 3 AWG | 0.2294 in | 26.7 mm² | 85 A | 100 A | 115 A | - |
| 2 AWG | 0.2576 in | 33.6 mm² | 95 A | 115 A | 130 A | - |
| 1 AWG | 0.2893 in | 42.4 mm² | 110 A | 130 A | 145 A | - |
| 1/0 AWG | 0.3249 in | 53.5 mm² | 125 A | 150 A | 170 A | - |
The last column is why a 14 AWG circuit stays on a 15 A breaker even though its 90 °C ampacity reads 25 A. Small conductors have little thermal mass, so the code limits their overcurrent protection regardless of the ampacity table.
Six loads and the rows they produce
Each line below is a calculator run. The first figure is the current, the rest is what the breaker and wire table prints for it.
12.5 A - 15 A breaker and 14 AWG if it cycles; running all evening it counts as continuous, 15.625 A, so 20 A and 12 AWG
20 A - 20 A and 12 AWG for a short draw; as a continuous load 25 A, which calls for a 25 A breaker and 10 AWG
40 A - 40 A and 8 AWG on paper; charging for hours is continuous, 50 A, so a 50 A breaker and 6 AWG
5 A - far below the smallest standard breaker of 15 A; on low-voltage DC the cable length matters more than the breaker
12.5 A - the same current as the 1,500 W heater, because 1,200 ÷ 0.8 = 1,500 VA
30.533 A - per line at power factor 1; a 35 A breaker and 8 AWG, or 40 A and 8 AWG if continuous (38.166 A)
Relationships behind the numbers
How to read the breaker and wire rows
The result prints two rows because the same appliance can land on either side of the continuous-load line. Use the first row when the load switches on and off, like a hair dryer or a microwave. Use the second when it runs for three hours or more at a stretch, like a space heater on a cold night, a water heater recovering, or an EV charger.
| Situation | Interpretation | Example |
|---|---|---|
| Current at or below 80% of the breaker | Fits either load type | 12.5 A on a 20 A breaker |
| Between 80% and 100% of the breaker | Only for loads under 3 hours | 16.5 A on a 20 A breaker |
| Above the breaker rating | Needs a larger breaker and wire | 21 A on a 20 A breaker |
| Above 125 A | Outside this table, service or feeder sizing | 130 A continuous |
These rows are a planning aid, not a design. Motor circuits follow NEC Article 430, long runs need a voltage-drop check, more than three current-carrying conductors or a hot attic reduce ampacity, and local codes amend the NEC. A licensed electrician should confirm any circuit before it is wired.
Amps questions, with the numbers worked
Related tools
Electrical Power Calculator
Watts, VA and kWh from volts and amps, with single- and three-phase AC - Open the calculator
Parallel Plate Capacitor Calculator
Capacitance of two or more plates from their area, gap and dielectric, in pF, nF or µF - Open the calculator
Ohm's Law Calculator
Volts, amps or ohms from the other two, and the series resistor for an LED - Open the calculator
Electrical Cable Calculator
Cable length and cross-section for an installation run - Open the calculator
Electricity Usage Calculator
Monthly kWh and cost for household appliances - Open the calculator
Thermal Conductivity Calculator
Heat flow through a material from its conductivity, area and thickness - Open the calculator
Mechanical Power Calculator
Watts from work and time, or from force and speed - Open the calculator
See also
Calculator verified by the LiczGrupa.pl team
Content, formulas and results have been reviewed for accuracy and relevance by our team of specialists.

Reviewed by: Natalia Skrzek